
16.2.2 Configuration rules
The input identifier can be a device
or
a special sensor (outside temperature,
setpoint adjuster).
Rules for inputs
Multiple use of inputs is possible, no limitations.
Only inputs with compatible units are offered for input "wiring".
Alarming for inputs is only active if the input is connected prior to the end of
commissioning.
If an input identifier changes, all related settings are changed automatically
without explicit information (e.g., P-band Xp is changed automatically from 30 K
to 500 Pa if the processed identifier is changed from temperature to pressure).
Order of configuration:
Procedure for extra
configuration
–
First basic configuration, then extra configuration.
Connection methods:
–
Always from arrow ( ) to line (
).
–
From uppercase to uppercase.
–
From lowercase to lowercase.
–
From function to input: "x" to "x".
–
From output block to output terminal: Analog "Y" to "Y".
–
Relay "Q" to "Q".
The result of logic block 1 is provided to logic block 2. As a result, the result from
logic block 1 is provided at logic block 2 in the same process. This allows for best
possible timing to process RMS705B input signals.
Example for good
configuration
200 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies
Appendix
01.04.2010