Main menu > Commissioning > Settings > ....
or
Setting values
Main menu > Settings > Faults > Fault relay 1…2 >
Operating line
Range
Factory setting
Fault priority
Urgent, Not urgent, All
All
Indication of fault
Fault internally (optically), Fault
internally (audibly), Fault via bus
(audibly) **
Fault internally
(audibly) *
Inversion Yes,
No
No
* Factory setting for "Fault relay 2": "Fault via bus (audibly)".
** Max. 1 bus fault message can be processed (even if the priorities are different). Recommendation: Do
not configure 2 bus fault relays.
At menu item "Aggregates", the state of the 2 fault relays can be read.
Display values
Main menu > Aggregates > Faults >
Operating line
Current state
Fault relay 1
Off, On
Fault relay 2
Off, On
12.6 Function check / wiring test
During the wiring test, the two fault relays can be enabled directly:
Wiring test
Main menu > Commissioning > Wiring test > Outputs >
Operating line
Comment
Fault relay 1
Off, On
Fault relay 2
Off, On
181 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies
Faults
01.04.2010