9.3.3
Assign texts
You can assign a specific text to each "Signal doubler-inverter". This text is
displayed as menu and operating line text on the operating pages.
Main menu > Commissioning > Settings > ....
or
Main menu > Settings > Signal converter > Signal doubler-inverter >
Operating line
Range
Factory setting
Signal doubler-inverter
Max. 20
characters
Signal doubler-inverter
Setting values
See Section 16.4 "Editable texts RMS705B" for an overview of all editable texts
and on how to reset them.
9.3.4
Function check / wiring test
The current state (inputs/outputs) of the signal doubler inverter is displayed on the
operator unit.
Main menu > Signal converter > Signal doubler-inverter >
Display values
Operating line
Comment
Preselection external*
%, °C, ----
Modulating output A
0...100 %
Modulating output B
0...100 %
* Dependent on the input identifier.
You can directly control "Signal doubler-inverter" during the wiring test.
Main menu > Commissioning > Wiring test > Outputs >
Wiring test
Operating line
Comment
Split-Inv output A
----, 0...100 %
Split-Inv output B
----, 0...100 %