15 Electrical
connections
15.1 Connection rules
CE- CE-
CE+ CE+ X1
X2
X3
X4
X5
X6
X8
X7
G
G
Q14
N
PE
Q12
Pump
Low-voltage side
Mains voltage side
Konnex bus
Double terminal
with internal
connection
Auxiliary terminals
in the control panel
2-speed fan
Passive sensor /
signal source /
contact sensing
Active sensor /
signal source
Actuator
DC 0...10 V
Terminal connection
concept
Only 1 solid wire
or
1 stranded wire can be connected to each terminal (cage
terminal).
Note
31
40
Z
13
Connection procedure
with spring cage
terminals
1.
2.
3.
1. Strip wire (length 7...8 mm; for module connector RMZ780: length 8…9 mm).
Steps
2. Connect wire using a screwdriver (size 0 to 1; for module connector: size 0).
3. Apply pressure with screwdriver while inserting the wire.
4. Remove
screwdriver.
196 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies
Electrical connections
01.04.2010