6.3.4
Maintenance message
A maintenance message can be assigned to each operating hours counter,
e.g.: "Service Fan SA".
Both "Text for: Service required" and "Service interval" are freely selectable.
"Service interval" specifies the number of operating hours until the next service. No
maintenance message is sent if "Service interval" is set to 0 h.
The fault priority is set to "Not urgent".
Main menu > Commissioning > Settings > …
or
Select interval and enter
text for maintenance
Main menu > Settings > Data acquisition > Operating hours > Operating hours 1…4 >
Operating line
Range
Factory setting
Service interval
0…99999 h
0 h
Text for: Service required
Max. 20 characters
[O'hrs 1] serv req
A corresponding maintenance message is generated once the counter "Operating
hours since service" reaches the value for the maintenance interval.
No. Text
Effect
1911
[O'hrs 1] serv req
Non-urgent fault.
1912
[O'hrs 2] serv req
Non-urgent fault.
1913
[O'hrs 3] serv req
Non-urgent fault.
1914
[O'hrs 4] serv req
Non-urgent fault.
Maintenance messages
6.3.5
Operating hours display
Main menu > Data acquisition > Operating hours 1…4 >
Display values
Operating line
Range
Factory setting
Operating hours x*
Display 0…99,999 h
Operating hours since service
Display 0…99,999 h
Reset** No,
Yes
No
* Display of the operating hours run to date. The counter counts to max. 99,999 hours and then rolls
over to 0.
** This setting resets "Operating hours since service" to 0 hours and deletes the maintenance message.