6.3.1
Activate the operating hours counter
Each counter is activated by assigning an input.
Main menu > Commissioning > Extra configuration> Data acquisition > Operating hours >
Configuration
Operating line
Range
Factory setting
Input 1
---, N.X1, N.X2, ...
---
Input 2
---, N.X1, N.X2, ...
---
Input 3
---, N.X1, N.X2, ...
---
Input 4
---, N.X1, N.X2, ...
---
6.3.2
Assign texts
A specific text can be assigned to each counter. This text is displayed as menu and
operating line text on the operating pages.
Main menu > Commissioning > Settings >…
or
Free text
Main menu > Settings > Data acquisition > Operating hours > Operating hours 1...4 >
Operating line
Range
Factory setting
Operating hours x
Max. 20 characters
Operating hours x
See Section 16.4 "Editable texts RMS705B" for an overview of all editable texts
and on how to reset them.
6.3.3
Set operating hours counter
Service staff can set the operating hours counter to a defined value or 0. This value
runs on the operating hours counter.
After 99999 hours, the counter automatically returns to 0. This value can only be
changed at the password level.
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Data acquisition > Operating hours > Operating hours 1…4 >
Set operating hours
counter to start value
Operating line
Range
Factory setting
Operating hours x
0..99999 h,
settable in increments of 1.
0 h
50 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies Data
acquisition
01.04.2010