11.4 General limiter
N.X1
N.X2
31
24
Z
22
en
You can select a general limiter function.
The limitation function overrides the normal control function of the controller.
See Section 11.4.2 for this function.
11.4.1 Enable function
Assign an input to the function to enable this function.
Main menu > Commissioning > Extra configuration > Controller 1...3 > Inputs >
Configuration
Operating line
Adjustable values / Comment
General limit controller
---, N.X1, N.X2, ..., internal analog
(analog values only)
Enable general limitation.
Main menu > Commissioning > Settings > ....
or
Main menu > Settings > Controller 1...3 > General limiter >
Setting values
Operating line
Range
(dependent on
selected type)
Factory setting
(type-dependent)
Limit value high
35.0 °C
Limit value low
16.0 °C
Differential high
0...100 K
50 K
Differential low
0...100 K
50 K
Reduction min
limitation cooling
0...10 K
0.0 K
P-band Xp
15 K, 10 %, 5 g/kg, 10 kJ/kg,
100 W/m2, 50 m/s, 10 bar,
50 mbar, 50 Pa, 100 ppm, 10.0, 50
Integral action time Tn
00.00...60.00 m.s 01.00 m.s
Main menu > Controller 1...3 >
Display values
Operating line
Comment
Actual value general limiter
172 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies
Universal controller
01.04.2010