Use setting "Request evaluation" to determine if the max value or the average of
the requests is to be used.
Request evaluation
When using the "Maximum" setting, the flow temperature is readjusted so that
the valve position for the consumer with the greatest heat demand is 90%.
When using the "Average" setting, the flow temperature is readjusted so that the
valve positions of the 4 largest consumers are 90% on average
Note
: This setting does not ensure that all consumers can cover their
refrigeration demand. It prevents, however, an individual consumer from forcing
the flow temperature to low levels (e.g. because a window was left open).
10.2.5 Internal refrigeration demand
RMS705B provides the calculated request signals as internal signals. To this end,
function block "Refrigeration demand" offers two outputs.
Purpose and function
( d)
The demand as a digital value, e.g. via a motor block, logic block, etc., can be
further handled, e.g., to switch on a pump when a refrigeration demand signal
was sent.
( a)
For example as setpoint for setpoint shift, differential control.
10.2.6 Refrigeration demand relay (Q )
Release for an external refrigeration source, for example, can be connected to this
output.
Purpose and function
The refrigeration demand relay responds as soon as the bus requests refrigeration.
Meaning:
Contact open
=
No refrigeration demand.
Contact closed =
Refrigeration demand.
Main menu > Commissioning > Extra configuration > Aggregates > Refrigeration demand >
Configuration
Operating line
Adjustable values / Comment
Refrigeration demand relay
---, N.Q1, N.Q3, ... / Enable output.
10.2.7 Refrigeration demand continuous ( )
In addition to the refrigeration demand relay, the refrigeration demand can be
provided at a continuous output for other devices.
Purpose
Main menu > Commissioning > Extra configuration > Aggregates > Refrigeration demand >
Configuration
Operating line
Adjustable values / Comment
Refrig demand modulating
---, N.Y1, N.Y2 / Enable output.