2-speed fan control by motor block.
Example
DO
DI
N.Q1
N.Q2
N.X1
X
You can set a "Runup time" and "Rundown time" for the 2-speed motor.
Runup time / Rundown
time
Settings
Main menu > Commissioning > Settings > ....
or
Main menu > Settings > Aggregates > Motor > Motor 1...6 >
Operating line
Range
Factory setting
Runup time
00.00... 59.59 m.s
00.10 m.s
Rundown time
00.00... 59.59 m.s
00.10 m.s
TiRup
TiCst
0
0
0
Speed 2
Speed 1
Off
Function diagram
TiRup = Runup
time
TiCst = Rundown
time
Key
109 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies
Aggregates
01.04.2010