9.3
Signal doubler/inverter
a
Y a
Y a
S p lit-In v
A
B
The function block provides the following functions:
Purpose
Limit the upper and lower input signal value, for output signal "Modulating output
A" or "Modulating output B" respectively.
Invert output signals "Modulating output A" or "Modulating output B".
Convert the signal of a passive input signal to two active signals.
Double the signal.
The output signals are provided in the range DC 0…10 V
or
as an internal, analog
signal (a).
9.3.1
Enable block
Assign an input to the function to enable this function.
Main menu > Commissioning > Extra configuration > Signal converter > Signal doubler-
inverter >
Configuration
Operating line
Adjustable values / Comment
Preselection external
---, N.X1, N.X2, ...
Modulating output A
---, N.Y1, N.Y2, ... /
enable modulating output.
Modulating output B
---, N.Y1, N.Y2, ... /
enable modulating output.
9.3.2
Settings
You can set the output signal of the modulating outputs for each output as an upper
and lower value.
Main menu > Commissioning > Settings > ....
or
Setting values
Main menu > Settings > Signal converter > Signal doubler-inverter >
Operating line
Range
Factory setting
Value low A
-50…+9999 %, °C
0, type-dependent.
Value high A
-50…+9999 %, °C
50, type-dependent.
Positioning signal min A*
0...100 %
0 %
Positioning signal max A*
0...100 %
100 %
Inversion A
No, Yes
No
Value low B
-50…+9999 %, °C
50, type-dependent.
Value high B
-50…+9999 %, °C
100, type-dependent.
Positioning signal min B*
0...100 %
0 %
Positioning signal max B*
0...100 %
100 %
Inversion B
No, Yes
No
* The settings impact only signal Y, not the corresponding internal, analog output signal (a).
134 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies Signal
converter
01.04.2010