Only one clock time master per system allowed. A fault message is displayed (on
the masters) if several devices are parameterized as master.
Note
Always synchronize the system, i.e. use master-slave mode (1 master, all other
devices are slaves).
Recommendation
4.1.3
Troubleshooting
RMS705B generates a fault message with regard to date and time in the following
cases:
Possible cases
If the clock on the bus is missing and the local clock is parameterized as time-of-
day slave, operation continues on the internal clock and fault message "System
time failure" is generated.
Fault message ">1 clock time master" is displayed if several devices are
parameterized as clock time master on the bus.
Fault message "Invalid time of day" is displayed if RMS705B loses its time
setting after power failure and/or if the time is not resent via bus.
Note 1: The clock in RMS705B has a backup battery for typically 48 and at
least 12 hours. The time must be reset if a power failure exceeds these hours.
Note 2: A flashing fault LED indicates invalid clock time.
No. Text
Effect
5001 System time failure
Non-urgent message; must not be
acknowledged.
5002 >1 clock time master
Non-urgent message; must be acknowledged.
5003 Invalid time of day
Non-urgent message; must not be
acknowledged.
Fault messages
4.2
Select language
Each device type has a number of languages loaded.
Action on initial startup
When switching on RMS705B for the first time, the "
Language
" menu is displayed
in English, regardless of the device type’s language set.
Select the required language from that menu.
The language can also be changed later during operation.
The following languages are loaded, depending on the device type:
Language selection
Type
Language 1
Language 2
Language 3
Language 4
Language 5
Language 6
RMS705B-1
German
French
Italian
Spanish
Portuguese
RMS705B-2
German
French
Dutch
English
RMS705B-3
Danish
Finnish
Norwegian
Swedish
RMS705B-4
Polish
Czech
Hungarian
Russian
Slovakian
Bulgarian
RMS705B-5
Greek
Romanian
Slovenian
Serbian
Croatian
Turkish
RMS705B-6
Chinese
Main menu > Commissioning > Settings > ....
or
Main menu > Settings > Device >
Setting values
Operating line
Range
Factory setting
Language
English
25 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies
General settings
01.04.2010