11.2.2 Troubleshooting
If no aggregates are configured for the control sequences, the "Current setpoint"
is displayed as "---".
When the commissioning menu is exited, a check is carried out to see if the
main controlled variable exists.
If the main controlled variable
or
differential input is missing, the corresponding
universal controller is switched off and a fault message is triggered (see "Fault
messages").
No.
Text
Effect
3011
[Main contr var 1] sensor error
Urgent message; must not be
acknowledged.
3012
[Main contr var 2] sensor error
Urgent message; must not be
acknowledged.
3013
[Main contr var 3] sensor error
Urgent message; must not be
acknowledged.
Fault messages
11.2.3 Control parameters (P-band, integral action time,
derivative action time)
For every sequence, a P-band (Xp), an integral action time (Tn), and a derivative
action time (Tv) can be set.
Integral action time Tn = 00:00 m.s: The controller has no I-part (PD).
Notes
Derivative action time Tn = 00:00 m.s: The controller has no D-part (PI).
Main menu > Commissioning > Settings > …
or
Setting values
Main menu > Settings > Controller 1...3 > Control parameters >
Operating line
Range
(type-dependent)
Factory setting
(type-dependent)
[Sequence 1 \_ ] Xp
30 K
[Sequence 1 \_ ] Tn
00.00…59.55 m.s
03.00 m.s
[Sequence 1 \_ ] Tv
00.00…59.55 m.s
00.00 m.s
[Sequence 4 _/ ] Xp
30 K
[Sequence 4 _/ ] Tn
00.00…59.55 m.s
03.00 m.s
[Sequence 4 _/ ] Tv
00.00…59.55 m.s
00.00 m.s
11.2.4 Control timeout
You can enter a control timeout period, for example, to prevent the cooling valve
from opening immediately after the heating valve closes.
The controller does not add the integral action part during that period of time.
Main menu > Commissioning > Settings > …
or
Setting values
Main menu > Settings > Controller 1...3 > Control parameters >
Operating line
Range
Factory setting
Control timeout
00.00…59.55 m.s
00.00
169 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies
Universal controller
01.04.2010