14.3 Resolve errors
Question
Answer
During commissioning, the wrong language
was selected.
Where do I find my language?
1. Press the ESC and OK buttons simultaneously.
2. Select the password level and enter
112
for password (same
as international emergency call).
3. Press "OK" to confirm.
The device activates English.
4. Select "Settings > Device > Language" to go to the desired
language.
RMS705B is completely off, but the
following is displayed:
"Operation locked, Remote operation".
How do I restart RMS705B?
Remote operation (OCI700.1) set RMS705B to commissioning
mode, which locked local operation.
If RMS705B is not restarted correctly via remote operation, it
remains in this state.
You can only restart RMS705B locally by briefly disconnecting
it from power.
Menu "Commissioning" does not allow for
navigation to "Main menu".
The following text is displayed:
"Caution! Invalid settings, Start not
possible".
H
ow do I restart RMS705B?
Configuration was not completely downloaded via the service tool
(OCI700.1).
Reload the configuration with the service tool (OCI700.1),
or
reconfigure RMS705B via the operator unit.
Fault message "[N.X4] sensor error" cannot
be acknowledged.
When exiting the "Commissioning" menu, a check is made to
see which sensors are connected.
If one of the sensors connected is missing later, a fault
message appears.
If a sensor was incorrectly wired and is rewired later, a "false"
fault message may be generated.
Resolve error:
Select "Commissioning" (Caution! Plant stops), then back to
"Main menu" (Caution! Plant starts).
The unit is "°C" rather than …???
Configuration error:
An input of a disabled function block was configured.
RMS705B in this case automatically displays "°C".
Resolve error:
E
nable the corresponding function block.
Flow signal not working?
Wrong values were entered for "Flow switching value on/Off".
Resolve error:
Select "Settings > Motor > Motor 1… > Flow switching value