Operate
6.2 Parameter description
SITRANS VP300 with or without HART
78
Operating Instructions, 03/2011, A5E01258666-03
"2.2.4 DI 2 Direction of action"
Factory setting:
Standard
Setting options:
Standard
Inverted
Purpose:
To adjust to normally closed contact (NC) or a normally open contact
(NO).
Description:
Use this parameter to set the direction of action of the input.
Standard: Digital input DI 2 is active when the contact on terminal
21/22 is closed or when there is voltage on terminal 11/12 (signal
status "Low").
Inverted: Digital input DI 2 is active when the contact on terminal
21/22 is open or when there is voltage on terminal 11/12 (signal
status "High").
"2.2.5 DO 1 Function"
Factory setting:
Deviation
Options:
Maintenance required
Maintenance demanded
Maintenance alarm
DI 1 Digital input
DI 2 Digital input
DI 3 Digital input
A1 Alarm limit
A2 Alarm limit
Deviation
Not in automatic mode
Output inverted
Purpose:
Specifying settings for output of error message and fault message.