Operate
6.2 Parameter description
SITRANS VP300 with or without HART
Operating Instructions, 03/2011, A5E01258666-03
83
6.2.2.4
"2.4 Extended setup"
Use this menu to set the alarm limits and the direction of action of these limits. The following
table contains an overview of the menus and parameters:
2.4.1 Setpoint
2.4.2 Free characteristic curve
2.4.3 Controller parameters
"2.4.1 Setpoint"
Use this menu to adjust setpoint processing to the special requirements of the application.
The following table contains an overview of the menus and parameters:
2.4.1.1 Direction
2.4.1.5 Characteristic curve
2.4.1.2 Limiting setpoint rate
2.4.1.6 Current 0%
2.4.1.3 Setpoint rate up
2.4.1.7 Current 100%
2.4.1.4 Setpoint rate down
"2.4.1.1 Direction"
Factory setting:
Standard
Setting options:
Standard
Inverted
Purpose:
Change direction of setpoint.
Description:
Use this parameter to reverse the direction of action of the setpoint.
The change in direction of action is mainly used for single-acting
actuators with the safety position "Up".
"2.4.1.2 Limiting setpoint rate"
Factory setting:
Off
Setting options:
Off
On
Auto