Operate
6.2 Parameter description
SITRANS VP300 with or without HART
98
Operating Instructions, 03/2011, A5E01258666-03
"3.5.1.7 Total time"
Requirements:
A partial stroke test has been performed.
Factory setting:
0.0 s
Display range:
0.0 ... 100.0
Purpose:
Indicates the total time of the lastpartial stroke test.
Description:
The total time includes the complete motion sequence of a partial
stroke test from the outset, including the breakaway time, stroke time,
adjustable pause time, and return time to the starting point.
"3.5.1.8 Last test"
Conditions:
A partial stroke test has been performed.
Factory setting:
0 hours
Display range:
0 ... 8760
Purpose:
Indicates the time elapsed since the last partial stroke time, in hours.
"3.5.1.9 Next test"
Conditions:
Partial stroke test is activated.
Factory setting:
0 hours
Display range:
0 ... 8760
Purpose:
Indicates the time remaining until the next partial stroke test will be
initiated automatically.
"3.5.2 PST Basic settings"
This menu is used to make settings for the partial stroke test. The following table contains an
overview of the menus and parameters:
3.5.2.1 Start position
3.5.2.6 Rate
3.5.2.2 Start tolerance
3.5.2.7 Pause
3.5.2.3 Stroke amount
3.5.2.8 Failure reaction
3.5.2.4 Direction of stroke
3.5.2.9 DO 1 Pulse length
3.5.2.5 Ramp mode