Operate
6.2 Parameter description
SITRANS VP300 with or without HART
84
Operating Instructions, 03/2011, A5E01258666-03
Purpose:
To suppress rapid changes of the setpoint.
Description:
The setpoint rate is effective in automatic mode and limits the speed
of change of the effective setpoint.
When switching from manual mode to automatic mode, the setpoint
rate adjusts the effective setpoint to the setpoint on the positioner.
This smooth switchover from manual mode to automatic mode
prevents excessive increases in pressure in long pipelines.
"2.4.1.3 Setpoint rate up" (Page 84)
"2.4.1.4 Setpoint rate down" (Page 84)
"2.4.1.3 Setpoint rate up"
Requirements:
The "On" option is set in the "2.4.1.2 Limiting setpoint rate" (Page 83)
parameter.
Factory setting:
100.0 %/s
Setting range:
0.1 ... 100.0 %/s
Purpose:
To suppress rapid changes of the setpoint.
"2.4.1.4 Setpoint rate down"
Requirements:
The "On" option is set in the "2.4.1.2 Limiting setpoint rate" (Page 83)
parameter.
Factory setting:
100.0 %/s
Setting range:
0.1 ... 100.0 %/s
Purpose:
To suppress rapid changes of the setpoint.
"2.4.1.5 Characteristic"
Factory setting:
Linear
Setting options:
Linear
1:25
1:33
1:50
1:25 inverse
1:33 inverse
1:50 inverse
Free characteristic curve
Purpose:
To linearize non-linear valve characteristic curves.
Description:
Use this parameter to linearize non-linear valve characteristic curves.
Any flow characteristics can be simulated by linear valve
characteristic curves.