Operate
6.2 Parameter description
SITRANS VP300 with or without HART
116
Operating Instructions, 03/2011, A5E01258666-03
"3.6.7.3 Status"
Requirements:
Activation of the monitoring function.
"3.6.7.1 Activation" (Page 115)
Message text:
Off
Ready
Reference measurement
First measurement
Valid value
Pause
Purpose:
Information on the actual status of calculation for the average
position value.
Description:
The following messages are shown in the display, depending on the
progress or status of the average position value calculation:
Off: The function is not active.
Ready: "Activation" parameter is set to "On". Start the monitoring
function with the "Start" parameter.
Reference measurement: Reference position value is currently
being determined.
First measurement: Reference value was determined. The next
value, the average position value, is now determined.
Valid value: A valid average position value is available.
Pause: Measurement interrupted by user.
See also
"3.6.7.4 Threshold 1" to "3.6.7.6 Threshold 3"
Requirements:
Monitoring function is activated.
"3.6.7.1 Activation" (Page 115)
Factory setting:
With "3.6.7.4 Threshold 1": 2
With "3.6.7.5 Threshold 2": 5
With "3.6.7.6 Threshold 3": 10
Setting range:
0.1 ... 100.0
Identical setting range for each threshold