Operate
6.2 Parameter description
SITRANS VP300 with or without HART
Operating Instructions, 03/2011, A5E01258666-03
119
"3.6.9.2 Unit"
Factory setting:
°C
Setting options:
°C
°F
Purpose:
Define temperature unit.
Description:
Use this parameter to set the temperature unit "°C" or "°F".
The selected temperature unit then also applies to all other
temperature-related parameters or values.
"3.6.9.3 Threshold 1" to "3.6.9.5 Threshold 3"
Requirements:
Monitoring function is activated.
"3.6.9.1 Activation" (Page 118)
Factory setting:
With "3.6.9.3 Threshold 1": 75 °C
With "3.6.9.4 Threshold 2": 80 °C
With "3.6.9.5 Threshold 3": 90 °C
Setting range:
-40.0 ... 90.0 °C
90.0 ... 194.0 °F
Identical setting range for each threshold.