Operate
6.2 Parameter description
SITRANS VP300 with or without HART
92
Operating Instructions, 03/2011, A5E01258666-03
6.2.3.3
"3.3 Initialization values"
You can use this submenu to display the adjusted values that are determined during the
initialization. The indicated values cannot be changed. The parameters are as follows:
Menu entry
Designation
Unit
3.3.1
Travel range
Percent [%], millimeters [mm], or degrees [°]
3.3.2
Travel time up
seconds [s]
3.3.3
Travel time down
seconds [s]
3.3.4
Lower endstop
Percent [%], millimeters [mm], or degrees [°]
3.3.5
Upper endstop
Percent [%], millimeters [mm], or degrees [°]
6.2.3.4
"3.4 Results"
The following table contains an overview of the menus and parameters:
3.4.1 Number of strokes
3.4.9
Setpoint current
3.4.2 Number of direction changes
3.4.10 General valve fault
3.4.3 Number of fault messages
3.4.11 Slipstick effect
3.4.4 A1 Number of alarms 1
3.4.12 Shift lower endstop
3.4.5 A2 Number of alarms 2
3.4.13 Shift upper endstop
3.4.6 Reset counters
3.4.14 Reference value of position
3.4.7 Operating hours
3.4.15 Average value of position
3.4.8 Operating hours since last initialization
"3.4.1 Number of strokes"
Purpose:
Movements of the actuator are summed up and displayed in this
parameter.
Description:
The distance covered is displayed in 100% strokes. Partial strokes are
summed up into 100% strokes. A 100% stroke corresponds to the
complete one-time travel distance, e.g. from UP→DOWN or
DOWN→UP.
"3.4.2 Number of direction changes"
Purpose:
Number of direction changes are counted and displayed in this
parameter.
Description:
Only direction changes are counted which exceed a threshold of
0.25%.