Technical data
10.9 Position feedback module
SITRANS VP300 with or without HART
162
Operating Instructions, 03/2011, A5E01258666-03
Without explosion protection
With explosion protection Ex "ia", "ic",
"nA"
Alarm module
6DR6003-8A
6DR6003-6A
1 switching contact input (terminals 21/22; galvanically connected with basic device, can only be connected to floating
contact)
Signal status
Low
Floating contact, open
High
Floating contact, closed
Contact load
< 3 V, < 15 μA
Connected loads
-
U
o
= ≤ 5.9 V
I
o
= ≤ 0,2 mA
P
o
= ≤ 1,2 mW
C
o
= ≤ 1 μF
L
o
= ≤ 1 mH
Test voltage
DC 840 V, 1 s
1)
Switching thresholds for supply to EN 60947-5-6: U
H
= 8.2 V, R
i
= 1 kΩ)
10.9
Position feedback module
Without explosion protection
With explosion protection Ex "ia", "ic",
"nA"
Position feedback module
6DR6003-8J
6D6003-6J
1 DC output for position feedback
2-wire connection
Rated signal range
4 ... 20 mA, protected against polarity reversal
Dynamic range
3,6 ... 20.5 mA
Fault current
1)
2.4 to 3.6 mA
External load R
B
[kΩ]
≤ (U
H
[V] - 12 V)/i [mA]
Transmission error
< 0,3 %
Temperature influence
≤ 0.1%/10 K
Resolution
< 0,05 %
Ripple content
< 0,1 %
For connecting to circuits with the
following peak values
See Chapter Electrical specifications (Page 156)
Galvanic isolation
Electrically isolated from the basic device
Test voltage
DC 840 V, 1 s
1)
In case of device fault or failure of setpoint power I
w