Operate
6.2 Parameter description
SITRANS VP300 with or without HART
68
Operating Instructions, 03/2011, A5E01258666-03
"1.3.4 Nominal stroke"
Requirements:
The nominal stroke is known.
Factory setting:
Linear actuator: 0.0 mm/part-turn actuator: 0.0°
Setting range:
Linear actuator: 0.0 ... 60.0 mm/part-turn actuator: 0.0 ... 120.0°
Purpose:
Enter nominal stroke of the actuator. For linear actuator in mm; for
part-turn actuator in °.
Description:
Obtain the nominal stroke from the nameplate of the actuator, if
indicated, or determine it by other means (by measuring, referring to
the data sheet, etc.).
"1.3.5 Actual position"
Requirements:
You have blocked the actuator and made a note of the actual
position of the actuator.
The compressed air is switched off.
Factory setting:
Linear actuator: 0.0/part-turn actuator: 0.0
Setting range:
0.0 ... 100.0 %
Purpose:
To set the actual position in which the actuator has been blocked.
"1.3.6 Travel time"
Requirements:
The approximate travel time is known.
Factory setting:
3 ... 20 s