![Siemens SITRANS VP300 Operating Instructions Manual Download Page 64](http://html.mh-extra.com/html/siemens/sitrans-vp300/sitrans-vp300_operating-instructions-manual_384840064.webp)
Operate
6.2 Parameter description
SITRANS VP300 with or without HART
62
Operating Instructions, 03/2011, A5E01258666-03
6.2
Parameter description
6.2.1
"1 Quick start" main menu
The following menus offer all initialization types and summarize the most frequently used
parameters. For most applications, installation and start-up can be carried out using the sub-
menus of the "1 Quick Start" main menu. The other main menus relate to special
applications.
The following table contains an overview of the setting options in this main menu:
1.1 Automatic initialization
1.3.2 Actuator direction
1.1.1 Actuator type
1.3.3 Tight closing
1.1.2 Tight closing
1.3.4 Nominal stroke
1.1.3 Initialize
1.3.5 Actual position
1.2 Manual initialization
1.3.6 Travel time
1.2.1 Actuator type
1.3.7 Adopt values
1.2.2 Tight closing
1.4 Reset
1.2.3 Initialize
1.4.1 Reset initialization
1.3 Device replacement
1.4.2 Factory setting
1.3.1 Actuator type
1.4.3 Stroke calibration
6.2.1.1
"1.1 Automatic initialization"
Initialization runs automatically. In the process, the positioner sequentially determines the
direction of action, the actuator travel or rotation angle, and the travel times of the actuator,
and adjusts the controller parameters to the dynamic response of the actuator.
"1.1.1 Actuator type"
Factory setting:
Linear <= 60 mm (2.36")
Setting options:
Part-turn
Linear <= 60 mm (2.36")
Linear > 60 mm (2.36")
Purpose:
Setting of appropriate actuator type for which the positioner is to be
initialized.