Operate
6.2 Parameter description
SITRANS P500 with HART
Operating Instructions, 12/2014, A5E02344528-09
127
Purpose:
Setting of the delay time for a calibration alarm
Description:
This parameter sets the delay period for the calibration alarm. The delay
period is the time which elapses between a calibration request and a cali-
bration alarm.
"3.5.1.5 Warn.-Alarm active"
Factory setting:
Off
Adjustment range:
•
Off
•
Timer on
•
Request on
•
Request and alarm on
Purpose:
Activate/ deactivate the calibration request or alarm
Description:
This parameter sets whether you have activated a calibration request and /
or a calibration alarm.
"Off"
Neither a calibration request/ alarm nor the timer is
activated.
"Timer on"
The timer is activated.
"Request on"
A calibration request is activated.
"Request and
alarm on"
A calibration request and an alarm are activated.
See also
Calibration timer and service timer (Page 164)
"3.5.1.6 Acknowledge/Reset"
Note
This parameter is displayed only if "3.5.1.5 Warn.-Alarm active" (Page 127) is not set to
"Off".
Display:
•
Acknowledging a request
•
Acknowledging an alarm
•
Resetting the timer
Purpose:
Acknowledging calibration requests and alarms, and resetting the timer
Description:
This parameter allows you to acknowledge an outstanding request or alarm.
Furthermore, "3.5.1.2 Timer" (Page 126) and "3.5.1.3 Warning" (Page 126)
can also be reset.