Operate
6.2 Parameter description
SITRANS P500 with HART
94
Operating Instructions, 12/2014, A5E02344528-09
"2.1.5.19 Density Unit"
Factory setting:
g/cm
3
Adjustment range:
g/cm
3
, kg/m
3
, lb/Gal, lb/ft
3
, g/ml, kg/l, g/l, lb/in
3
, ug/l, ug/m
3
Purpose:
Selection of the unit for the density parameter
Description:
This parameter allows you to select the unit for the measured density value.
"2.1.5.20 Density"
Factory setting:
1 g/cm
3
Adjustment range:
Freely selectable numeric value
Purpose:
Setting the value for the density
Description:
This parameter allows you to set the value for the density of the medium,
which is used for conversion between volume and mass.
Adjust the settings for the measurement range when you change the values
for density!
"2.1.6 Level"
Note
This menu item is only visible if "Level" was selected in "2.1.1 PV Select" (Page 83).
See also
Measuring mode "Level" (Page 145)
"2.1.6.1 Level Unit"
Factory setting:
m
Adjustment range:
ft, m, inch, cm, mm
Purpose:
Selection of the unit for the level measurement type
Description:
This parameter allows you to select the unit for the level measurement type.
The parameters associated with this unit are automatically converted into
the new unit.
"2.1.6.2 Level LRV"
Factory setting:
0 m
Adjustment range:
Freely selectable numeric value