Operate
6.2 Parameter description
SITRANS P500 with HART
Operating Instructions, 12/2014, A5E02344528-09
83
"1.1.12 Alarmselect"
Factory setting:
Deep
Setting range:
•
High
•
Deep
Purpose:
Selection of the fault current
Description:
You can select whether the lower or the upper fault current is to be output in the
case of a fault or alarm.
"High" The upper fault current is output in the case of a fault or alarm.
"2.2.3.2 Upper Alarm Current" (Page 101)
"Deep" The lower fault current is output in the case of a fault or alarm.
"2.2.3.1 Lower Alarm Current" (Page 101)
"1.1.13 Measvaluedisplay"
Factory setting:
PV unit
Setting range:
•
PV unit
•
%
•
mA
Purpose:
Selection of the PV display
Description:
This parameter allows you to select whether you wish to display the main
indication value as a digital measured variable in the respective unit as a
percentage output value or as a current value in mA.
6.2.3
"2 Setup"
6.2.3.1
"2.1 Input"
"2.1.1 PV Select"
Factory setting:
Pressure
Setting range:
•
Pressure
•
Volume flow
•
Mass flow
•
Level
•
Volume
•
Mass
•
User characteristic