Operate
6.2 Parameter description
SITRANS P500 with HART
Operating Instructions, 12/2014, A5E02344528-09
129
Purpose:
Set delay for a sensor service alarm
Description:
This parameter sets the delay period for the sensor service alarm. The delay
period is the time which elapses between a sensor service request and a
sensor service alarm.
"3.5.2.5 Warn.-Alarm active"
Factory setting:
Off
Adjustment range:
•
Off
•
Timer on
•
Request on
•
Request and alarm on
Purpose:
Activate/ deactivate the sensor service request or alarm
Description:
This parameter sets whether you have activated a sensor service request
and / or a sensor service alarm.
"Off"
Neither a sensor service request/ alarm nor the timer is
activated.
"Timer on"
The timer is activated.
"Request on"
A sensor service request is activated.
"Request and
alarm on"
A sensor service request and alarm are activated.
See also
Calibration timer and service timer (Page 164)
"3.5.2.6 Acknowledge/Reset"
Note
This parameter is displayed only if "3.5.2.5 Warn.-Alarm active" (Page 129) is not set to
"Off".
Adjustment range:
•
Acknowledge Warning
•
Acknowledge Alarm
•
Reset Timer
Purpose:
Acknowledging sensor service requests and alarms, and resetting the timer
Description:
This parameter allows you to acknowledge an outstanding request or alarm.
Furthermore, "3.5.2.2 Timer" (Page 128) and "3.5.2.3 Warning" (Page 128)
can also be reset.