Service and maintenance
10.3 Cleaning
SITRANS P500 with HART
Operating Instructions, 12/2014, A5E02344528-09
193
can be replaced. However, the scope of functions is limited to the function of existing
components.
If a combination of certain firmware versions of measuring cell and application electronics is
not possible for technical reasons, the device will identify this problem and go into "Fault
current" mode. This information is provided via the HART interface.
10.3
Cleaning
WARNING
Dust layers above 5 mm
Danger of explosion in hazardous areas. Device may overheat due to dust build up.
•
Remove dust layers in excess of 5 mm.
NOTICE
Penetration of moisture into the device
Device damage.
•
Make sure when carrying out cleaning and maintenance work that no moisture
penetrates the inside of the device.
Cleaning the enclosure
●
Clean the outside of the enclosure and the display window using a cloth moistened with
water or a mild detergent.
●
Do not use aggressive cleaning agents or solvents. Plastic components or painted
surfaces could be damaged.
WARNING
Electrostatic charge
Danger of explosion in hazardous areas if electrostatic charges develop, for example, when
cleaning plastic enclosures with a dry cloth.
•
Prevent electrostatic charging in hazardous areas.
10.3.1
Servicing the remote seal measuring system
The remote seal measuring system usually does not need servicing.