Connecting
5.4 Connecting the M12 connector
SITRANS P500 with HART
60
Operating Instructions, 12/2014, A5E02344528-09
5.4
Connecting the M12 connector
Procedure
CAUTION
A conductive connection must not exist between the shield and the connector housing.
WARNING
The connector may only be used for Ex ia devices and non-Ex devices; otherwise the
safety required for the approval is not guaranteed.
Note
Observe the protection class of the M12 connector when defining the protection class.
For devices in which a connector is already available on the housing, the connection is
established using a cable jack.
1.
Thread the parts of the cable jack as described by the connector manufacturer.
2.
Strip approximately 18 mm of the bus cable
①
.
3.
Twist the shield.
4.
Thread the shield in the insulating sleeve.
5.
Draw 8 mm of shrink sleeve over the cable, wires and shield up to the reference edge
②
.
6.
Screw the cable ends and the shield in the pin insert.
7.
Fix the parts of the cable jack as described by the connector manufacturer.
Figure 5-3
Preparing the connecting cable
①
Reference edge for stripping
③
Insulating sleeve over the shield
②
Reference edge for the dimension
specifications for cable assembly
④
Shrink sleeve