Technical data
11.4 Measuring accuracy
SITRANS P500 with HART
Operating Instructions, 12/2014, A5E02344528-09
201
11.4
Measuring accuracy
Differential pressure and flow rate measuring accuracy
Reference conditions
according to IEC 60770-1
•
Rising characteristic curve
•
Start of scale value 0 kPa/bar/psi
•
Seal diaphragm stainless steel
•
Measuring cell with silicone oil filling
•
Room temperature 25°C (77°F)
•
Vertical installation of the device
Measuring span ratio r (spread, Turn-Down)
r = maximum measuring span/set measuring span
Total Performance
•
Linear characteristic
r
≤
5
5 < r ≤ 10
5 kPa/50 mbar/20 inH
2
O
≤ 0,27
%
≤ 0,46
%
25 kPa/250 mbar/100 inH
2
O
≤ 0,14
%
≤ 0,27
%
25 kPa/1250 mbar/502 inH
2
O
625 kPa/6250 mbar/2509 inH
2
O
3200 kPa/32 bar/465 psi
≤ 0,09
%
≤ 0,14
%
•
Root extraction characteristic
Flow > 50 %
r
≤
5
5 < r
≤
10
•
5 kPa/50 mbar/20 inH
2
O
≤ 0,27
%
≤ 0,46
%
•
25 kPa/250 mbar/100 inH
2
O
≤ 0,14
%
≤ 0,27
%
•
25 kPa/1250 mbar/502 inH
2
O
625 kPa/6250 mbar/2509 inH
2
O
3200 kPa/32 bar/465 psi
≤
0,09 %
≤
0,14 %
Flow 25 ... 50 %
r
≤
5
5 < r
≤
10
•
5 kPa/50 mbar/20 inH
2
O
≤ 0,54
%
≤ 0,92
%
•
25 kPa/250 mbar/100 inH
2
O
≤ 0,28
%
≤ 0,54
%
•
25 kPa/1250 mbar/502 inH
2
O
625 kPa/6250 mbar/2509 inH
2
O
3200 kPa/32 bar/465 psi
≤
0,18 %
≤
0,28 %
Conformity error at limit point setting, including
hysteresis and repeatability
•
Linear characteristic
r ≤
10
r ≥
10
5 kPa/50 mbar/20 inH
2
O
≤ 0,06
%
≤
(0.006
•
r) %
25 kPa/250 mbar/100 inH
2
O
1.25 bar/1250 mbar/502 inH
2
O
625 kPa/6250 mbar/2509 inH
2
O
3200 kPa/32 bar/465 psi
≤
0,03 %
≤
(0.003
•
r) %
•
Root extraction characteristic
Flow > 50 %
r ≤
10
r ≥
10