Operate
6.2 Parameter description
SITRANS P500 with HART
102
Operating Instructions, 12/2014, A5E02344528-09
6.2.3.3
"2.3 Simulation"
"2.3.1 Output Current"
"2.3.1.1 Fixed Current"
Factory setting:
Off
Adjustment range:
•
Off
•
On
Purpose:
Activate / deactivate the constant current simulation
Description:
This parameter allows you to activate or deactivate the constant current
simulation.
"2.3.1.2 Fixed Current Value"
Factory setting:
4 mA
Setting range:
Min: 3.55 mA
Max: 23.0 mA
Purpose:
Setting the constant current value
Description:
This parameter allows you to set the value for the output current to be used
for simulation purposes.
"2.3.2 Pres. Simulation"
"2.3.2.1 Select Simulation"
Factory setting:
Off
Setting range:
•
Off
•
Fixed pressure value
•
Pressure ramp
Purpose:
Selection of pressure simulation
Description:
This parameter allows you to select whether a pressure should be simulat-
ed.
"Fixed pressure
value"
Simulation of a fixed pressure value.
"Pressure ramp"
Simulation of a pressure ramp.
See also
Simulation as fixed value (Page 159)
Simulation with a ramp function (Page 159)