Technical data
11.4 Measuring accuracy
SITRANS P500 with HART
202
Operating Instructions, 12/2014, A5E02344528-09
Differential pressure and flow rate measuring accuracy
•
5 kPa/50 mbar/20 inH
2
O
≤ 0,06
%
≤
(0.006
•
r) %
•
25 kPa/250 mbar/100 inH
2
O
1.25 bar/1250 mbar/502 inH
2
O
625 kPa/6250 mbar/2509 inH
2
O
3200 kPa/32 bar/465 psi
≤ 0,03
%
≤ (0.003
•
r) %
Flow 25 ... 50 %
r ≤
10
r ≥
10
•
5 kPa/50 mbar/20 inH
2
O
≤ 0,12
%
≤
(0.012
•
r) %
•
25 kPa/250 mbar/100 inH
2
O
1.25 bar/1250 mbar/502 inH
2
O
625 kPa/6250 mbar/2509 inH
2
O
3200 kPa/32 bar/465 psi
≤
0,06 %
≤
(0.006
•
r) %
Ambient temperature influence
In percent per 28 °C (50 °F)
•
5 kPa/50 mbar/20 inH
2
O
≤
(0.04
•
r + 0.05) %
•
25 kPa/250 mbar (100 inH
2
O)
≤
(0.025 •
r + 0.014) %
•
1.25 bar/1250 mbar/502 inH
2
O
625 kPa/6250 mbar/2509 inH
2
O
3200 kPa/32 bar/465 psi
≤
(0.006
•
r + 0.03) %
Effect of static pressure
•
At the start-of-scale value
5 kPa/50 mbar/20 inH
2
O
≤
(0.1
•
r) % per 7 MPa/70 bar/1015 psi correction
via zero point correction
25 kPa/250 mbar (100 inH
2
O)
≤
(0.035
•
r) % per 7 MPa/70 bar/1015 psi correc-
tion via zero point correction
1.25 bar/1250 mbar/502 inH
2
O
625 kPa/6250 mbar/2509 inH
2
O
3200 kPa/32 bar/465 psi
≤
(0.007
•
r) % per 7 MPa/70 bar/1015 psi correc-
tion via zero point correction
•
On the span
5 kPa/50 mbar/20 inH
2
O
≤ 0.13 % per 7
MPa/70 bar/1015 psi
25 kPa/250 mbar/100 inH
2
O
1.25 kPa/1250 mbar/502 inH
2
O
≤ 0.03 % per 7
MPa/70 bar/1015 psi
625 kPa/6250 mbar/2509 inH
2
O
≤ 0.09 % per 7
MPa/70 bar/1015 psi
3200 kPa/32 bar/465 psi
≤ 0.05% per 7
MPa/70 bar/1015 psi
Long-term stability
In 5 years ≤
0.05
•
r %
In 10 years ≤
0.08
•
r %
Step response time T
63
(without electrical damping)
5 kPa/50 mbar/20 inH
2
O
≤
140
ms, contains a dead time of ≤
45 ms
25 kPa/250 mbar/100 inH
2
O
1.25 kPa/1250 mbar/502 inH
2
O
625 kPa/6250 mbar/2509 inH
2
O
3200 kPa/32 bar/465 psi
≤
88 ms, contains a dead time
of ≤
45 ms