Connecting
5.1 Basic safety instructions
SITRANS P500 with HART
54
Operating Instructions, 12/2014, A5E02344528-09
WARNING
Lack of equipotential bonding
Danger of explosion through compensating currents or ignition currents through lack of
equipotential bonding.
•
Ensure that the device is potentially equalized.
Exception: It may be permissible to omit connection of the equipotential bonding for devices
with type of protection "Intrinsic safety Ex i".
WARNING
Unprotected cable ends
Danger of explosion through unprotected cable ends in hazardous areas.
•
Protect unused cable ends in accordance with IEC/EN 60079-14.
WARNING
Improper laying of shielded cables
Danger of explosion through compensating currents between hazardous area and the non-
hazardous area.
•
Only ground shielded cables that run into the hazardous area at one end.
•
If grounding is required at both ends, use an equipotential bonding conductor.
WARNING
Connecting device in energized state
Danger of explosion in hazardous areas.
•
Connect devices in hazardous areas only in a de-energized state.
Exceptions:
•
Circuits of limited energy may also be connected in the energized state in hazardous
areas.
•
Exceptions for type of protection "Non-sparking nA" (Zone 2) are regulated in the
relevant certificate