Commissioning
8.3 Differential pressure and flow rate
SITRANS P500 with HART
Operating Instructions, 12/2014, A5E02344528-09
183
8.3.4
Commissioning with vapor
①
Pressure transmitter
⑦
Drain valves
②
Stabilizing valve
⑧
Condensate pots
③
,
④
Differential pressure valves
⑨
Differential pressure transducer/Orifice
plate
⑤
Differential pressure lines
⑩
Insulation
⑥
Shut-off valves
Figure 8-1
Measuring steam
Requirement
All valves are closed.
Procedure
WARNING
Hot vapor
Danger of injury or damage to device.
If the shut-off valves
⑥
and the differential pressure valve
③
are both open and the
stabilizing valve
②
is then opened, the pressure transmitter
①
can be damaged by the
flow of vapor.
•
Follow the specified procedure for commissioning.