Operate
6.2 Parameter description
SITRANS P500 with HART
Operating Instructions, 12/2014, A5E02344528-09
97
"2.1.8 Mass"
"Note re: mass"
Note
This menu item is only visible if "Mass" was selected in "2.1.1 PV Select" (Page 83).
See also
Measuring mode "Mass" (Page 149)
"2.1.8.1 Mass Unit"
Factory setting:
kg
Setting range:
g, kg, MetTon, lb, ShTon, LTon, ounce
Purpose:
Selection of the unit for the mass measurement type
Description:
This parameter allows you to select the unit for the mass measurement
type. The parameters associated with this unit are automatically converted
into the new unit.
"2.1.8.2 Mass LRV"
Factory setting:
0 kg
Adjustment range:
Freely selectable numeric value
Purpose:
Setting the start of scale value
Description:
This parameter allows the start of scale value for the mass scaling to be set.
The value that is set for "2.1.2.1.2 Setting LRV" (Page 84) or "2.1.2.2.2 Set
LRV with Pressure" (Page 85) is automatically assigned to this value.
The start of scale value is expressed in the units you selected under "2.1.8.1
Mass Unit" (Page 97).
"2.1.8.3 Mass URV"
Factory setting:
1000 kg
Adjustment range:
Freely selectable numeric value
Purpose:
Setting the full scale value
Description:
This parameter allows the full scale value for the mass scaling to be set.
The value that is set for "2.1.2.1.3 Setting URV" (Page 84) or "2.1.2.2.3 Set
URV with Pressure" (Page 85) is automatically assigned to this value.
You can enter the end of scale value in the unit selected under "2.1.8.1
Mass Unit" (Page 97).