Operate
6.3 Description of the operating functions
SITRANS P500 with HART
156
Operating Instructions, 12/2014, A5E02344528-09
See also
Volume flow "1.1.6.1 Transfer Function" (Page 73)
Mass flow "1.1.7.1 Transfer Function" (Page 75)
Application point"srlin" and "sroff"
The output current for the "srlin" function is displayed linearly below the application point of
the square-rooted characteristic. For the function "sroff" the output current is set to zero.
Characteristic "srlin"
Characteristic "sroff"
Application point "srlin2":
The function "srlin2" has a variable application point. The range up to this point contains two
linear characteristic sections. The first section ranges from the zero point to 0.6% of the
output value and 0.6% of the pressure value. The second section runs at a steeper gradient
up to the root application point for the root extraction that you chose.
Characteristic "srlin2"