Operate
6.3 Description of the operating functions
SITRANS P500 with HART
158
Operating Instructions, 12/2014, A5E02344528-09
①
Linear control range
②
lower saturation limit (factory setting)
③
upper saturation limit (factory setting)
④
lower fault current value (factory setting)
⑤
upper fault current value (factory setting)
⑥
Recommended setting range for lower fault current range and lower control range limit
⑦
Recommended setting range for upper fault current range and upper control range limit
Figure 6-16 Current limits
See also
"2.2.2 Current Limits" (Page 100)
6.3.7
Simulation
6.3.7.1
Overview of simulation
Description
With the "Simulation" diagnostic function, you can receive and further process simulated
measurement data onsite or in the control room without having process pressure value. This
allows you to run individual process sequences in the "cold" state and thus simulate process
states. In addition, if you inject simulation values you can test the line routing from the control
room to the individual pressure transmitter.
The simulation of the current can also be set as a fixed value and that of the pressure can
also be performed as a ramp function.