Operate
6.2 Parameter description
SITRANS P500 with HART
126
Operating Instructions, 12/2014, A5E02344528-09
6.2.4.5
"3.5 Diagnostic Setup"
"3.5.1 Calibration Interval"
"3.5.1.1 Status"
Note
This parameter is displayed only if there is an outstanding calibration request or alarm.
Display:
•
Request acknowledged
•
Alarm acknowledged
•
Request outstanding
•
Alarm outstanding
Purpose:
Displays the calibration status
Description:
This parameter displays outstanding calibration requests and alarms.
"3.5.1.2 Timer"
Factory setting:
0
Display:
In [h]
Purpose:
Displays the status of the calibration timer
Description:
'This parameter shows the time which has passed since the start of the
calibration timer.
See also
Calibration timer and service timer (Page 164)
"3.5.1.3 Warning"
Factory setting:
0
Adjustment range:
In [h]
Purpose:
Setting the time after which a calibration request will be made
Description:
This parameter sets the time after which a calibration request will be made.
"3.5.1.4 Alarm Delay"
Factory setting:
0
Setting range:
In [h]