Engineering and remote access
7.7 Web server
Power supply system SITOP PSU8600
278
Manual, 09.2018, A5E36758446-5-76
7.7.6
Diagnostics
7.7.6.1
Alarms
The SITOP PSU8600 system internally saves a total of 1024 alarm entries. Of these, there
are a maximum of the last 256 entries in the web, sorted according to time of display.
Using the "Severity filter", the list can be restricted to the following degrees of severity:
●
NORMAL/INFO
●
MAINTENANCE REQUIRED
●
MAINTENANCE DEMANDED
●
DIAGNOSIS
1.
Click on "Save under" to save the list of alarms as CSV file.
Proceed as follows to display the active alarms or the alarm history:
1.
Select menu "Diagnostics".
2.
Select submenu "Alarms" and the required entry.
Active alarms
The currently active system alarms are provided in this list.
Alarm history
The alarm history is provided in this list.
Note: After a system restart, the last 50 open alarms before the restart are displayed
(separated by "Reboot"). When the power is interrupted for a longer period of time, the date
and time of the alarm entries can be lost, whereby the alarm sequence is retained.
The alarm list is completely cleared by pressing "Clear history".