Display name
Data type
Definition
Description
Alarm_F_Overtemperature
Boolean
PropertyType
Buffer component overtemperature
detected. Depending on the system
configuration, buffering is either
restricted or no longer possible.
Alarm_F_OvertemperatureModule Boolean
PropertyType
Buffer component overtemperature
detected. Depending on the system
configuration, buffering is either
restricted or no longer possible.
Alarm_F_SoftwareUpdating
Boolean
PropertyType
Performing firmware update.
Read/write access is currently not
possible.
Alarm_F_UnexpectedEmptySlotDe-
tected
Boolean
PropertyType
Unexpected empty slot detected
Alarm_F_UzkHigh
Boolean
PropertyType
Invalid internal supply voltage.
Buffer component disabled.
Alarm_F_WrongChecksum
Boolean
PropertyType
Defective firmware detected. De-
vice must be reactivated with a
new firmware update.
Alarm_MD_General
Boolean
PropertyType
General critical error occurred. The
device may therefore behave in-
consistently.
Alarm_MD_InconsitentBatteryType Boolean
PropertyType
Different battery types connected.
Only batteries of the same type can
be operated together.
Alarm_MD_LessCapableModule
Detected
Boolean
PropertyType
A module with reduced power was
detected. Deviating system behav-
ior may be possible.
Alarm_MD_ModuleParameters
Corrupt
Boolean
PropertyType
Stored module configuration is
corrupt. Deviating module behavior
may be possible.
Alarm_MR_NoBatteryConnected
Boolean
PropertyType
Attempting to access a battery that
is not available. Either the battery
with the requested number was
never connected or communication
with this battery was interrupted.
Alarm_MD_Overtemperature
Boolean
PropertyType
Danger of overtemperature detect-
ed in a system component. Imme-
diate load reduction is
recommended.
Alarm_MD_OvertemperatureMo-
dule
Boolean
PropertyType
Danger of overtemperature detect-
ed in a system component. Imme-
diate load reduction is
recommended.
Alarm_MD_ReverseBatteryPolarity
Detected
Boolean
PropertyType
Wrong battery polarity - check
battery connections.
Alarm_MR_BatteryCommunication
Disconnected
Boolean
PropertyType
Communication to the battery is
interrupted. Buffering is still possi-
ble, the battery charge level has
been reduced to a minimum how-
ever.