Troubleshooting
8.2 PROFINET alarm list
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
359
Channel
Error Type
Extended
Error Type
Severity Alarm text
Help text
257
11
MR
Buffer mode
The power supply system is supplied via the buffer
expansion module(s).
257
12
N
Device starting up.
Device starting up.
257
13
N
Device is in manual mode.
The device was switched to manual mode. Remote
configuration and control are not possible.
257
14
F
Expansion module is not avai-
lable.
Expansion module was not found. Power supply
system response deviates from the configuration.
257
15
F
Invalid number of modules.
Invalid number of modules detected. Invalid slot.
257
16
MR
New unconfigured module
detected.
New unconfigured module detected.
257
17
F
Invalid system configuration.
System configuration is incorrect. Normal operation
of the system is not possible.
257
18
MD
Stored system configuration is
corrupt.
Stored system configuration is corrupt. Deviations
from the expected response may occur outside nor-
mal operation.
257
19
MR
Invalid system configuration.
System configuration is different. The system can be
operated.
257
20
F
Hardware failure
A hardware failure has occurred. All outputs of the
power supply system have been switched off.
257
25
MR
Module with excessive power
detected.
A module with excessive power was detected. Nor-
mal operation of the system is possible.
257
26
MR
Unexpected module type de-
tected.
Unexpected module type detected.
257
27
MD
Module with reduced power
detected.
A module with reduced power was detected. Deviat-
ing system behavior may be possible.
257
28
F
Incompatible module detected. The module has a module type that is incompatible
with the configuration. The module cannot be com-
missioned.
257
29
F
Unexpected empty slot detect-
ed.
Unexpected empty slot detected.
257
30
N
Buffer mode
The primary power supply has failed; the power sup-
ply system is being supplied through the buffer com-
ponent.
257
31
N
Sufficient buffer readiness
Sufficient buffer readiness has been achieved; the
charge status of the buffer components in the system
has reached the preset threshold value.
257
32
N
Buffer readiness disabled
No buffering possible because the buffer component
has been disabled.
257
33
F
Unknown module found (slot 1). Unknown module found (slot 1).
257
34
F
Unknown module found (slot 2). Unknown module found (slot 2).
257
35
F
Unknown module found (slot 3). Unknown module found (slot 3).
257
36
F
Unknown module found (slot 4). Unknown module found (slot 4).
257
37
F
Unknown module found (slot 5). Unknown module found (slot 5).
257
38
F
Unknown module found (slot 6). Unknown module found (slot 6).
257
39
F
Unknown module found.
Unknown module found.