Engineering and remote access
7.8 OPC UA server
Power supply system SITOP PSU8600
320
Manual, 09.2018, A5E36758446-5-76
Display name
Data type
Definition
Description
Alarm_MR_UnexpectedModuleDetected Boolean
Sitop_8600_AlarmType
Unexpected module type detected.
Alarm_N_BufferDisabled
Boolean
Sitop_8600_AlarmType
Buffer deactivated.
Alarm_N_ChargingDisabledByCommand Boolean
Sitop_8600_AlarmType
Loading the buffer component(s)
using the control command deac-
tivated
Alarm_N_RestartAfterSafetyShutdown
Boolean
Sitop_8600_AlarmType
The device has been restarted
after an automatic shutdown.
Alarm_N_SerialnumberDiverge
Boolean
Sitop_8600_AlarmType
Different serial number detected.
Alarm_N_SetpointParametersOutOf
Range
Boolean
Sitop_8600_AlarmType
A parameter value is outside its
maximum value (e.g. the S7 at-
tempts to set 28.8 V; however, the
module can only provide 28.0 V,
and therefore goes into limiting).
Alarm_N_SoftwareVersionDiverge
Boolean
Sitop_8600_AlarmType
The alarm is displayed in conjunc-
tion with the alarm to replace the
module.
Alarm_N_SystemModeManual
Boolean
Sitop_8600_AlarmType
The device was switched to the
MANUAL mode. Control via the
PLC is now no longer possible.
Alarm_N_SystemStateStartup
Boolean
Sitop_8600_AlarmType
Information that the system will be
started.
Alarm_N_UCMBuffering
Boolean
Sitop_8600_AlarmType
Buffer mode.
Alarm_N_UCMReady
Boolean
Sitop_8600_AlarmType
Ready for buffering.
Alarm_N_ClientShutdownFinished
Boolean
Sitop_8600_AlarmType
Client run down.
Alarm_N_ClientShutdownInitiated
Boolean
Sitop_8600_AlarmType
System has initiated that the client
is run down.
Alarm_MR_BufferingNotPossible
Boolean
Sitop_8600_AlarmType
Buffering not possible.
Alarm_MR_BufferingInsufficientCharging Boolean
Sitop_8600_AlarmType
Module is not sufficiently charged
in order to be able to buffer.
Alarm_N_BufferingDisabledByCommand Boolean
Sitop_8600_AlarmType
Buffering remotely deactivated.
Alarm_N_ChargingDisabledByCommand Boolean
Sitop_8600_AlarmType
Charging remotely deactivated.
Alarm_MR_InputOvervoltage
Boolean
Sitop_8600_AlarmType
An overvoltage condition was de-
tected at the input.
Alarm_MR_InputUndervoltage
Boolean
Sitop_8600_AlarmType
Voltage at the input is too low.
Alarm_MD_ShutdownPrimary
Boolean
Sitop_8600_AlarmType
The resonance converter of the
power supply was shut down.
Alarm_MD_SystemConfigReadError
Boolean
Sitop_8600_AlarmType
The system configuration cannot
be read from the EEPROM.
Variables "ID" and "Severity" are assigned to each alarm.