Engineering and remote access
7.8 OPC UA server
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
341
Display name
Data type
Definition
Description
Alarm_N_SafetyBufferingExtension
Running
Boolean
PropertyType
The multiple buffer event over-
stress protection was activated,
because three buffer events oc-
curred within a minute.
Alarm_N_SerialnumberDiverge
Boolean
PropertyType
Different serial number detected
Alarm_N_SoftwareDownload
Boolean
PropertyType
The firmware download to the
system has been completed suc-
cessfully. A system reset is re-
quired to run the firmware update.
Alarm_N_SoftwareVersionDiverge Boolean
PropertyType
Different firmware version detected
Alarm_N_SOHTestRunning
Boolean
PropertyType
Battery 'State of Health' tests (SoH)
are performed.
Lock
Display name
Data type
Definition
Description
Lock
Object
LockingServiceType
See Section "Lock (Page 323)".
MethodSet
Display name
Data type
Definition
Description
UpdateFirmware
Method
-
Firmware update
StartCapacityTracingTest
Method
-
Battery 'State of Health' tests (SoH)
are started.
StopCapacityTracingTest
Method
-
Battery 'State of Health' tests (SoH)
are stopped.
ParameterSet
/
All variables of the SITOP UPS8600 UPS module are listed together under the
"ParameterSet" node.
Parameters not described otherwise, in alphabetical order:
Display name
Data type
Definition
Description
ModuleBatteryTestIntervalSetpoint Enumeration
MultiStateDiscrete-
Type
Interval in which the automatic
battery test is executed (0 = never,
1, …, 24 = every 1, …,24 hours)
ModuleBufferTimerSetpoint
Integer
AnalogItemType
Set time until the buffer timer ex-
pires in ms
ModuleBufferTimerEnableSetpoint Boolean
PropertyType
The buffer time is activated
ModuleMaximumChargingpo-
werSetpoint
Enumeration
MultiStateDiscrete-
Type
Maximum permissible charging
power (0 W = off, 60 W = low,
120 W = high)