Engineering and remote access
7.6 Cyclic and acyclic data
Power supply system SITOP PSU8600
232
Manual, 09.2018, A5E36758446-5-76
Slot
Subslot Data
Description
Value range
Data size
1-6
5
Channel4 Utarget
[10 mV]
see data "Channel 1"
Channel4 Ilimit
[10 mA]
Channel4 Ithreshold
Channel4
OutputEnable
Channel4 Reset_In
Data block active
6EP4436-8XB00-0DY0
Slot
Subslot Data
Description
Value range
Data size
1-6
2
Channel1 Utarget
[10 mV]
Currently set setpoint of the output
voltage for output 1.
4.0 V - 28.0 V
(default setting:
24.0 V)
Unsigned16
Channel1 Ilimit
[10 mA]
Response threshold of the output
current for output 1. When this is
exceeded, the output current is
interpreted as having an overload
condition and is shut down with a
time delay - or limited.
Output 2.5 A:
0.0 A - 2.5 A
(default setting: 2.5 A)
Unsigned16
Channel1 Ithreshold
Prewarning threshold of the confi-
gured response threshold for the
output current in %. An alarm is
initiated when the actual output
current exceeds this value. Opera-
tion is continued without any re-
strictions. Prewarning is
deactivated by entering "0 %".
0 - 100 %
(default setting: 90 %)
Unsigned8
Channel1
OutputEnable
Switches output 1 on or off. A pos-
sible automatic shutdown due to
overload or power failure is not
taken into account.
0 = false, >0 = true
(default setting: false)
Unsigned8
Channel1 Reset_In
Resets an overload shutdown for
this output
0 = false, >0 = true
(default setting: false)
Unsigned8
Data block active
Indicator: Data block contains valid
data.
0 = false, >0 = true
(default setting: false)
Unsigned8
1-6
3
Channel2 Utarget
[10 mV]
see data "Channel 1"
Channel2 Ilimit
[10 mA]
Channel2 Ithreshold
Channel2
OutputEnable
Channel2 Reset_In
Data block active
1-6
4
Channel3 Utarget
[10 mV]
see data "Channel 1"