![background image](http://html.mh-extra.com/html/siemens/sitop-psu8600/sitop-psu8600_manual_382606257.webp)
Engineering and remote access
7.6 Cyclic and acyclic data
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
257
Data
Description
Data type
Ilimit3 potentiometer [10mA]
Manually set threshold of the output current at
output 3. Response threshold of the output current
for an output set using the potentiometer at the
device. When this is exceeded, the output current
is interpreted as having an overload condition and
is shut down with a time delay - or limited.
Unsigned16
Output Enable3 manual button (0/255)
Actual DIP switch state for output 3:
•
0 = Manually switched off
•
255 = manually switched on
Unsigned8
Fill byte(s)
-
Unsigned8
Utarget4 potentiometer [10mV]
Manually set setpoint of the output voltage at out-
put 4: Setpoint of the output voltage for an output
manually set using the potentiometer at the device;
in normal operation, the output is controlled to this
setpoint voltage.
Unsigned16
Ilimit4 potentiometer [10mA]
Manually set threshold of the output current at
output 4. Response threshold of the output current
for an output set using the potentiometer at the
device. When this is exceeded, the output current
is interpreted as having an overload condition and
is shut down with a time delay - or limited.
Unsigned16
Output Enable4 manual button (0/255)
Actual DIP switch state for output 4:
•
0 = Manually switched off
•
255 = manually switched on
Unsigned8
Fill byte(s)
-
Unsigned8
Index 32: State information (reading)
Data
Description
Data type
Fill byte(s)
-
Unsigned16
Module operation state Operating state
0 = Off
Expansion module is shut
down.
Unsigned8
1 = ErrorOff
The expansion module
was automatically shut
down as a result of opera-
tion under inadmissible
operating conditions.
2 = ReadyForRestart
After an automatic shut-
down due to a fault, the
expansion module can be
reactivated by switching
off and switching on the
supply voltage.
3 = Boot
The expansion module is
powering up, all of the
outputs are still switched
off.