
Installation
6.7 Connecting the control contacts and signaling contacts of the UPS module
Power supply system SITOP PSU8600
162
Manual, 09.2018, A5E36758446-5-76
Signaling contacts
The signaling contacts are NO contacts, and allow information about the operating state of
the UPS module and the connected battery modules to be processed further.
Note
The contact rating is 30 V AC/0.5 A; 60 V DC/0.3 A; 30 V DC/1 A.
The signaling circuit must fully comply with the requirements relating to SELV circuits.
The function of the signaling contact is described in Chapter "UPS module (Page 36)".
You can obtain more information about the assignment of the signaling contacts in Chapter