Troubleshooting
8.2 PROFINET alarm list
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
363
Channel
Error Type
Extended
Error Type
Severity Alarm text
Help text
260
2
F
Communication problem
A communication problem exists between primary
and secondary side controllers. All outputs of the
power supply system have been switched off.
260
4
F
Communication problem
A communication problem exists between the
PROFINET module and the main controller.
260
7
MD
Wrong battery configuration
(battery index: {1:d})
Different battery types connected. Only batteries of
the same type can be operated together.
261
1
MD
Incompatible battery detected
The battery is a type that is not compatible with the
configuration. The battery cannot be commissioned.
261
2
MD
Module with reduced power
detected.
A module with reduced power was detected. Deviat-
ing system behavior may be possible.
261
3
MR
Module with excessive power
detected.
A module with excessive power was detected. Nor-
mal operation of the system is possible.
261
4
MR
Unexpected module type de-
tected.
Unexpected module type detected.
261
5
MR
New battery detected
New battery detected
261
6
MD
Unknown battery
Data from the battery cannot be read correctly. Bat-
tery is defective or not supported by SIEMENS.
261
7
MD
Wrong battery configuration
(battery index: {1:d})
Different battery types connected. Only batteries of
the same type can be operated together.
261
9
MR
Connection to battery interrupted Connection to battery interrupted
261
10
MR
Connection to battery interrupted Connection to battery interrupted - check connection
and fuse
261
11
MR
Deep discharge battery
Battery is deep discharged - no buffering possible.
261
12
MD
Fuse is defective (battery index:
{1:d})
Fuse is defective.
261
13
MD
Battery defective
Battery defective - neither buffer nor charging opera-
tion is possible
261
14
MR
Warning before battery over-
temperature
Battery temperature too high – battery life will be
shortened
261
16
MR
Warning before battery low
temperature
Battery temperature too low - reduced output current
261
18
MR
Battery parameters corrupt
The battery configuration is corrupt. The battery
behavior remains unchanged, however.
261
19
MD
Battery parameters corrupt
The battery configuration is corrupt. Battery behavior
may deviate.
261
20
N
Battery replacement recom-
mended (end of service life
near)
It is recommended to replace the battery because
the battery lifetime is approaching its calculated end
and there is a threat of restricted buffer readiness.
261
21
MR
Battery replacement required
(end of service life reached)
It is recommended to replace the battery because
the battery lifetime has reached its calculated end
and restricted buffer readiness is probable.
261
22
N
Battery lifetime counter has
been reset
The calculation of the battery lifetime was reset and
restarted after successful battery replacement.
261
23
N
Battery discharged
Battery is discharged - no buffering possible.
261
24
MR
Battery pack defective.
The battery pack is most likely defective and should
be replaced to avoid problems during buffering.