Troubleshooting
8.3 Alarm list web server
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
379
ID
Severity
Event
Help text
46
N
Different firmware version detected Different firmware version detected
47
MR
New unconfigured module detect-
ed.
New unconfigured module detected.
48
N
Different serial number detected
Different serial number detected
49
MR
Module with excessive power de-
tected.
A module with excessive power was detected. Normal oper-
ation of the system is possible.
50
MR
Unexpected module type detected. Unexpected module type detected.
51
MD
Module with reduced power de-
tected.
A module with reduced power was detected. Deviating sys-
tem behavior may be possible.
52
F
Incompatible module detected.
The module has a module type that is incompatible with the
configuration. The module cannot be commissioned.
53
F
Unexpected empty slot detected.
Unexpected empty slot detected.
54
MD
Battery not available
Attempt to access a battery that is not available. Either the
battery with the requested number was never connected or
communication with this battery was interrupted.
58
N
Buffer component disabled via
control contact
Buffer component disabled via control contact
59
MD
Wrong battery polarity
Wrong battery polarity - check battery connections.
60
MR
Communication to battery inter-
rupted
Communication with the battery is interrupted. Buffering is
still possible, but the battery charge is reduced to a mini-
mum.
61
MR
Power connection to battery inter-
rupted
Power connection to at least one battery interrupted. Check
power connection and fuse.
62
N
Battery SoH test
Battery 'State of Health' tests (SoH) are performed.
63
N
Buffer timer exceeded.
Buffer timer exceeded, system is turned off.
64
MD
Wrong battery configuration (bat-
tery index: {1:d})
Different battery types connected. Only batteries of the
same type can be operated together.
65
MR
Surplus battery
More than 6 batteries are connected. Connect a maximum
of 6 batteries to the Energy Storage Link.
66
MR
Battery on subslot 1 disconnected
during runtime
67
MR
Battery on subslot 2 disconnected
during runtime
68
MR
Battery on subslot 3 disconnected
during runtime
69
MR
Battery on subslot 4 disconnected
during runtime
70
MR
Battery on subslot 5 disconnected
during runtime
71
N
Buffering extension activated
1 minute buffering extension after third buffering event is
running.
72
N
Charging power reduced due to
high system load
The charging power has been reduced below its target val-
ue due to high system load.
73
N
Charging disabled due to high
system load
The charging has been disabled due to high system load.
Charging will continue automatically when free system load
is available again.