Engineering and remote access
7.6 Cyclic and acyclic data
Power supply system SITOP PSU8600
256
Manual, 09.2018, A5E36758446-5-76
Index 6: Device information (reading)
Data
Description
Data type
Order number
Article No./Order number
VisibleString(20)
Product state
Product release
Unsigned8
Fill byte(s)
-
Unsigned8
Software version
Software version
Unsigned32
Serial number
Serial number
VisibleString(16)
Index 7: Hardware settings (reading)
Data
Description
Data type
Utarget1 potentiometer [10mV]
Manually set setpoint of the output voltage at out-
put 1: Setpoint of the output voltage for an output
manually set using the potentiometer at the device;
in normal operation, the output is controlled to this
setpoint voltage.
Unsigned16
Ilimit1 potentiometer [10mA]
Manually set threshold of the output current at
output 1. Response threshold of the output current
for an output set using the potentiometer at the
device. When this is exceeded, the output current
is interpreted as having an overload condition and
is shut down with a time delay - or limited.
Unsigned16
Output Enable1 manual button (0/255)
Actual DIP switch state for output 1:
•
0 = Manually switched off
•
255 = manually switched on
Unsigned8
Fill byte(s)
-
Unsigned8
Utarget2 potentiometer [10mV]
Manually set setpoint of the output voltage at out-
put 2: Setpoint of the output voltage for an output
manually set using the potentiometer at the device;
in normal operation, the output is controlled to this
setpoint voltage.
Unsigned16
Ilimit2 potentiometer [10mA]
Manually set threshold of the output current at
output 2. Response threshold of the output current
for an output set using the potentiometer at the
device. When this is exceeded, the output current
is interpreted as having an overload condition and
is shut down with a time delay - or limited.
Unsigned16
Output Enable2 manual button (0/255)
Actual DIP switch state for output 2:
•
0 = Manually switched off
•
255 = manually switched on
Unsigned8
Fill byte(s)
-
Unsigned8
Utarget3 potentiometer [10mV]
Manually set setpoint of the output voltage at out-
put 3: Setpoint of the output voltage for an output
manually set using the potentiometer at the device;
in normal operation, the output is controlled to this
setpoint voltage.
Unsigned16