Engineering and remote access
7.7 Web server
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
285
The system runs up again after a system reset. All supplementary modules are internally
addressed, the system configuration checked and the PROFINET connection to the control
re-established.
Using a system reset, it is not possible to switch-on outputs again after an automatic
shutdown.
Procedure
1.
Select menu "Diagnostics".
2.
Select submenu "Online functions".
3.
Select the "Reset system" entry.
4.
In the editor area, click on "Reset system".
5.
Acknowledge the confirmation prompt with "OK".
Reset to factory settings
A reset to the factory settings deletes all hardware and software configurations stored in the
SITOP PSU8600 and restores the factory settings.
This influences, for example:
●
IP address
●
Device name
●
Parameter values for the SITOP PSU8600 and assigned supplementary modules
●
"Web server activated" setting. Web server is deactivated.
Procedure
1.
Select menu "Diagnostics".
2.
Select submenu "Online functions".
3.
Select entry "Reset to factory settings".
4.
In the editor area, click on "Reset to factory settings".
5.
Acknowledge the confirmation prompt with "OK".